很多电工反映,在对低压配电柜进行维护的时候会发现低压配电柜内或多或少都会有潮湿的现象,有的低压配电柜潮湿现象特别严重,周围的线缆被霉点覆盖,低压配电柜内的金属元器件也是锈迹斑斑,而且还经常出现跳闸的情况,有的甚引发火灾。
Many electricians report that when maintaining the low-voltage distribution cabinet, they will find that there will be moisture in the low-voltage distribution cabinet more or less. Some low-voltage distribution cabinets are particularly wet, the surrounding cables are covered with mildew, the metal components in the low-voltage distribution cabinet are also rusty, and trips often occur, and some even cause fires.
其实低压配电柜生锈发霉多是因为潮湿所引起的,当发现有潮湿现象的时候应该立刻采取措施进行防潮治理,接下来给大家分享一下低压配电柜的有效办法。
In fact, the rust and mildew of low-voltage distribution cabinet are mostly caused by moisture. When moisture is found, measures should be taken immediately for moisture-proof treatment. Next, let's share the effective methods of dehumidification of low-voltage distribution cabinet.
低压低压配电柜的有效办法:
Effective methods for dehumidification of low-voltage distribution cabinet:
利用停电机会清擦设备,使配电箱内保持清洁。
Take advantage of the power failure to clean the equipment to keep the distribution box clean.
密闭低压配电柜。高压室的通风窗、通风口,按规程规定落实空气过滤措施。使高压室内空气保持清洁。
Closed low voltage distribution cabinet. Air filtering measures shall be taken for the ventilation windows and vents of the high-pressure chamber according to the regulations. Keep the air in the high-pressure room clean.
低压配电柜厂家
Low voltage distribution cabinet manufacturer
低压配电柜下边的电缆沟、电缆隧道、电缆孔洞作防水密封,加装自然通风排潮通道,保持电缆隧道空气干燥。
The cable trench, cable tunnel and cable hole under the low-voltage distribution cabinet shall be waterproof sealed, and natural ventilation and moisture discharge channel shall be installed to keep the air in the cable tunnel dry.
室外低压配电柜可加装雨搭。
The outdoor low-voltage distribution cabinet can be equipped with rain tower.
出线户内封闭式母线桥底部铁板改为钢丝网板,或横向开一个l00mm的缝隙(靠近墙体的部位),雨水由出线穿墙套管固定钢板处进人时,可以从缝隙排出。不能进人开关柜。
The iron plate at the bottom of the indoor enclosed bus bridge of the outgoing line is changed into a steel wire mesh plate, or a l00mm gap is opened horizontally (near the wall). When the rainwater enters from the fixed steel plate of the outgoing line through the wall casing, it can be discharged from the gap. Do not enter the switch cabinet.
对于已经出现凝露状况,并且比较严重的话,建议使用SPR-NL防凝露装置或HK-SEPRI-T顶置系统,按湿度自动控制,排除柜内水分。
In case of serious condensation, it is recommended to use spr-nl anti condensation device or hk-sepri-t overhead dehumidification system to automatically control the humidity and remove the moisture in the cabinet.
The above is the new information provided by the imitation Rittal cabinet. For more highlights, please come from: http://www.tongyuhengcheng.com , we will share more wonderful content with you later